Skip to main navigation Skip to search Skip to main content

Estimating ASHRAE Guideline 36 energy savings for multi-zone variable air volume systems using Spawn of EnergyPlus

  • Kun Zhang
  • , David Blum
  • , Hwakong Cheng
  • , Gwelen Paliaga
  • , Michael Wetter
  • , Jessica Granderson
  • Lawrence Berkeley National Laboratory
  • Taylor Engineers
  • TRC Companies Inc.

Research output: Contribution to journal › Journal Article › peer-review

53 Citations (Scopus)

Abstract

ASHRAE Guideline 36 (G36) publishes high-performance control sequences for Variable Air Volume (VAV) system operation. Retrofitting existing VAV control sequences to G36 promises to have a large potential for energy savings. However, it is difficult to estimate the savings accurately and the process of doing so can be costly and time-consuming. This paper evaluates the energy use of a multi-zone VAV system with terminal reheat using the G36 sequences and compares it to a group of baseline control sequences that represent existing practices. Spawn of EnergyPlus is used for the whole building simulation, where the envelope is modelled in EnergyPlus and the HVAC equipment and its pressure-flow network and the control sequences are modelled in Modelica. The comparison of the control sequences performance is further conducted in parametric studies. For a medium-sized commercial building, the G36 sequences provide a wide range of HVAC energy savings with an average of 31%.

Original languageEnglish
Pages (from-to)215-236
Number of pages22
JournalJournal of Building Performance Simulation
Volume15
Issue number2
DOIs
Publication statusPublished - 2022
Externally publishedYes

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • ASHRAE Guideline 36
  • EnergyPlus
  • HVAC
  • Modelica
  • control sequences
  • energy efficiency

ASJC Scopus subject areas

  • Architecture
  • Building and Construction
  • Modeling and Simulation
  • Computer Science Applications

Fingerprint

Dive into the research topics of 'Estimating ASHRAE Guideline 36 energy savings for multi-zone variable air volume systems using Spawn of EnergyPlus'. These topics are generated from the title and abstract of the publication. Together, they form a unique fingerprint.

Cite this