TY - GEN
T1 - TEV Sensor-Based PD Measurements with a Focus on PRPD Patterns and FFT Analysis
AU - Abbasi, Mahdi
AU - Lachance, Mathieu
AU - David, Eric
N1 - Publisher Copyright:
© 2025 IEEE.
PY - 2025
Y1 - 2025
N2 - Assessing the insulation condition of high-voltage equipment using non-intrusive partial discharge (PD) measurement is widespread nowadays. The transient earth voltage (TEV) method, a relatively new non-intrusive approach, operates by detecting the surface current induced by electromagnetic waves (EM) propagating from PD, which spreads out through the discontinuities of the equipment's outer surface. This paper evaluates the performance of TEV sensors compared to the IEC 60270 standard for detecting PD caused by various defect types inside and outside a metal enclosure in a laboratory setting. Phaseresolved PD (PRPD) pattern and fast Fourier transform (FFT) indicate that each defect has its own characteristic. The FFT analysis reveals that PD can only be effectively detected at specific frequencies where it is distinguishable from background noise.
AB - Assessing the insulation condition of high-voltage equipment using non-intrusive partial discharge (PD) measurement is widespread nowadays. The transient earth voltage (TEV) method, a relatively new non-intrusive approach, operates by detecting the surface current induced by electromagnetic waves (EM) propagating from PD, which spreads out through the discontinuities of the equipment's outer surface. This paper evaluates the performance of TEV sensors compared to the IEC 60270 standard for detecting PD caused by various defect types inside and outside a metal enclosure in a laboratory setting. Phaseresolved PD (PRPD) pattern and fast Fourier transform (FFT) indicate that each defect has its own characteristic. The FFT analysis reveals that PD can only be effectively detected at specific frequencies where it is distinguishable from background noise.
KW - IEC 60270
KW - electromagnetic waves
KW - metal enclosure
KW - partial discharge
KW - transient earth voltage
UR - https://www.scopus.com/pages/publications/105016150597
U2 - 10.1109/EIC63069.2025.11123381
DO - 10.1109/EIC63069.2025.11123381
M3 - Contribution to conference proceedings
AN - SCOPUS:105016150597
T3 - 2025 IEEE Electrical Insulation Conference, EIC 2025
BT - 2025 IEEE Electrical Insulation Conference, EIC 2025
PB - Institute of Electrical and Electronics Engineers Inc.
T2 - 2025 IEEE Electrical Insulation Conference, EIC 2025
Y2 - 8 June 2025 through 11 June 2025
ER -