Résumé
This study presents a comparative performance analysis of a direct expansion geothermal evaporator using R410A, R407C and R22 as refrigerants. The main goal is to predict the best refrigerant capable of serving as a substitute for R22. A validated geothermal evaporator model developed by our research team was used. The simulation results show that for low refrigerant flow rate, the R410A DX evaporator shows better performance than that of R22, but from the pressure drop observed and superheating recorded with the former, it can be concluded that R407C is the best fluid to replace R22 in the DX GHP. That notwithstanding, to minimize pressure drop, especially for high refrigerant flow rates, R410A would be a better choice for the design of new DX systems.
| Langue originale | Anglais |
|---|---|
| Pages (de - à) | 306-317 |
| Nombre de pages | 12 |
| Revue | Applied Thermal Engineering |
| Volume | 82 |
| Les DOIs | |
| État | Publié - 5 mai 2015 |
SDG des Nations Unies
Ce résultat contribue à ou aux Objectifs de développement durable suivants
-
SDG 7 – Energie propre et d'un coût abordable
Classification disciplinaire ASJC Scopus
- Ingénierie énergétique et technologie de l'énergie
- Ingénierie industrielle et de fabrication
Empreinte digitale
Voici les principaux termes ou expressions associés à « A comparative performance study of a direct expansion geothermal evaporator using R410A and R407C as refrigerant alternatives to R22 ». Ces libellés thématiques sont générés à partir du titre et du résumé de la publication. Ensemble, ils forment une empreinte digitale unique.Citer cette ressource