Skip to main navigation Skip to search Skip to main content

A study of interfacial pressure behavior for two types of thermally cycled coldshrinkable joints

  • Hydro-Quebec

Research output: Contribution to journal › Journal Article › peer-review

17 Citations (Scopus)

Abstract

Joints are generally known to be the weakest link of underground distribution lines. One of the most common failure modes is attributable to the occurrence of dielectric breakdown at the cable-joint interface. Interfacial pressure is known to be a key factor in the interfacial breakdown strength: a high interfacial pressure leads to good dielectric breakdown strength whereas a lower pressure leads to poor long-term performance. The present work shows the behavior of two different types of distribution cable joints: ethylene-propylene rubber (EPR) based coldshrinkable cable joint and silicone rubber (SR) based cold-shrinkable cable joint. Interfacial pressure was monitored for thermal cycles at three different temperatures: 75, 90 and 130°C. The cycling protocol is based on existing IEEE standard for cable joints for use with extruded dielectric cables rated 5-138 kV. A preliminary theoretical model has been developed and compared to the obtained data.

Original languageEnglish
Pages (from-to)476-480
Number of pages5
JournalConference Record of IEEE International Symposium on Electrical Insulation
DOIs
Publication statusPublished - 2002

ASJC Scopus subject areas

  • Building and Construction
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'A study of interfacial pressure behavior for two types of thermally cycled coldshrinkable joints'. These topics are generated from the title and abstract of the publication. Together, they form a unique fingerprint.

Cite this