Passer à la navigation principale Passer à la recherche Passer au contenu principal

A study of interfacial pressure behavior for two types of thermally cycled coldshrinkable joints

  • Hydro-Quebec

Résultats de recherche: Contribution à un journal › Article publié dans une revue, révisé par les pairs › Revue par des pairs

17 Citations (Scopus)

Résumé

Joints are generally known to be the weakest link of underground distribution lines. One of the most common failure modes is attributable to the occurrence of dielectric breakdown at the cable-joint interface. Interfacial pressure is known to be a key factor in the interfacial breakdown strength: a high interfacial pressure leads to good dielectric breakdown strength whereas a lower pressure leads to poor long-term performance. The present work shows the behavior of two different types of distribution cable joints: ethylene-propylene rubber (EPR) based coldshrinkable cable joint and silicone rubber (SR) based cold-shrinkable cable joint. Interfacial pressure was monitored for thermal cycles at three different temperatures: 75, 90 and 130°C. The cycling protocol is based on existing IEEE standard for cable joints for use with extruded dielectric cables rated 5-138 kV. A preliminary theoretical model has been developed and compared to the obtained data.

Langue originaleAnglais
Pages (de - à)476-480
Nombre de pages5
RevueConference Record of IEEE International Symposium on Electrical Insulation
Les DOIs
ÉtatPublié - 2002

Classification disciplinaire ASJC Scopus

  • Bâtiment et construction
  • Ingénierie électrique et électronique

Empreinte digitale

Voici les principaux termes ou expressions associés à « A study of interfacial pressure behavior for two types of thermally cycled coldshrinkable joints ». Ces libellés thématiques sont générés à partir du titre et du résumé de la publication. Ensemble, ils forment une empreinte digitale unique.

Citer cette ressource